Installation and Programming Manual
42
SYSTEM: SYSTEM CONTROL
Quick Key Item Default Explanation
1
↓↓
SYSTEM CONTROL --- Controls Specific System Operations
1 2 Quick Arm YES
if YES: eliminates the need for a User Code when arming to
the STAY or AWAY modes
if NO: a valid User Code is required for arming to STAY or
AWAY
1 2
02
Quick UO YES
if YES: a user may activate a Utility Output without the need
to enter a User Code
if NO: a User Code is required to activate a Utility Output
1 2 03 Allow Bypass YES
if YES: permits zone bypassing by authorized system users
after entering a valid User Code
if NO: zone bypassing is NOT permitted
1 2 04 Quick Bypass NO
if YES: eliminates the need for a valid User Code when
bypassing zones
if NO: qualified users must enter a valid User Code to
bypass zones
1 2 05 False Code Trouble YES
if YES: a False Code report (if enabled) will be sent to the
Central Station if there are three successive attempts
in which an incorrect User Code is entered when
arming or disarming. No alarm will sound at the
premises, but a trouble indication will appear on the
system’s keypad(s)
if NO: a local alarm will be sounded at the premises
1 2 06 Bell Squawk YES
if YES: a brief “chirp” will be produced from the system’s
external sounder(s) once the system is armed–at the
conclusion of the Exit Delay period
if NO: no “chirp” is produced
1 2 07 Bell 30/10 NO
if YES: any external sounder(s) will, after each 30 seconds of
operation, cease to sound for 10 seconds
if NO: an external sounder will operate without such
interruption
1 2 08 Alarm Phone Cut NO
if YES: activates the external sounder if the phone line is cut
or telephone service is interrupted
if NO: no such activation occurs
1 2 09 3-Minute Bypass YES
if YES: bypasses all zones automatically for 3 minutes when
power is restored to an “unpowered” system to allow
for the stabilization of motion and/or smoke detectors
if NO: no such bypassing occurs
1 2 10 Double Verification of
Fire Alarms
NO
if YES: after the detection of smoke or fire, the following
procedure is implemented to verify the condition:
power to the smoke detector(s) on the affected zone is
removed after 15 seconds, the power is restored if,
within 1 minute, a subsequent detection of the
condition occurs, the system will produce a fire alarm
if NO: no fire alarm verification will take place
1 2 11 Audible Panic NO
if YES: an external sounder(s) will operate when a “Police
Alarm” is initiated at the keypad
if NO: no external sounder operation will occur during a
keypad “Police Alarm”, making the alarm truly “silent”
(i.e. Silent Panic/Duress)
1 2 12 AC Report Delay NO
if YES: after 30 minutes without AC power, the system will
report the outage to the Central Station (if so
specified, see page 92)
if NO: the system will report the loss of AC to the Central
Station immediately (if so specified, see page 92)
1 2 13 BuzzeràBell NO
if YES: if an alarm occurs when the system is armed to the
STAY mode, each keypad will sound for 15 seconds
before the external sounder(s) will operate
if NO: an alarm in the STAY mode will cause each keypad
and any external sounder(s) to operate simultaneously
INSTALLER PROG:
1)SYSTEM ↓↓